Apcupsd на Centos 7
APC UPS SMART 1500, подключен по USB.
Настройка на сервере:
$ sudo yum -y install apcupsd
$ sudo nano /etc/apcupsd/apcupsd.conf UPSCABLE usb UPSTYPE usb LOCKFILE /var/lock SCRIPTDIR /etc/apcupsd PWRFAILDIR /etc/apcupsd NOLOGINDIR /etc ONBATTERYDELAY 6 BATTERYLEVEL 37 MINUTES 10 TIMEOUT 0 ANNOY 300 ANNOYDELAY 60 NOLOGON disable KILLDELAY 0 NETSERVER on NISIP 0.0.0.0 NISPORT 3551 EVENTSFILE /var/log/apcupsd.events EVENTSFILEMAX 10 UPSCLASS standalone UPSMODE disable STATTIME 0 STATFILE /var/log/apcupsd.status LOGSTATS off DATATIME 0
Проверяем:
$ sudo apcaccess
Настройка на клиенте:
[root@faust apcupsd]# cat apcupsd.conf | egrep "^[^#]" UPSCABLE ether UPSTYPE net DEVICE _IP_сервера:3551 LOCKFILE /var/lock SCRIPTDIR /etc/apcupsd PWRFAILDIR /etc/apcupsd NOLOGINDIR /etc ONBATTERYDELAY 6 BATTERYLEVEL 41 MINUTES 12 TIMEOUT 0 ANNOY 300 ANNOYDELAY 60 NOLOGON disable KILLDELAY 0 NETSERVER on NISIP 0.0.0.0 NISPORT 3551 EVENTSFILE /var/log/apcupsd.events EVENTSFILEMAX 10 UPSCLASS standalone UPSMODE disable STATTIME 0 STATFILE /var/log/apcupsd.status LOGSTATS off DATATIME 0